亚洲成av人片在线观看无下载丨亚洲日本欧美日韩中文字幕丨国产a毛片aaaaaa丨国产精品反差婊在线观看丨级精品无码久久久国片

Welcome to the official website of jiangsu libang electromechanical equipment co., LTD.

  • WeChat public number

  • Mobile web site
  • 中文

service hotline:

400-025-9918

NEWS

Industry dynamic

Location:Home > news > Industry dynamic - Problems with evaporator equipment are solved

Problems with evaporator equipment are solved
Release time:2018-6-8 11:22:04      Number of clicks:1943
1. The evaporator often fails to defrost
Evaporator electrical heating tube is very easy to burn out, and as the evaporator with heating tube series electric heating tube is made up of 2 a group, one of the burning, lines can not work normally, so the frost on the evaporator ontology can't melt.
2. The collecting pan freezes
Water dish inside is not set electric heating tube, although has the same electric heating wire and the water pipe, but power is very small, poor quality, often fails, due to the low temperature temperature reached - 18 ℃ below, after the evaporator defrosting, water entering the water pan is too late to discharge will regelation, cannot normal run off through the drain pipe.
3. The downpipe is blocked with ice
The electrical heating wire of the downpipe is out of order. Because the electric heating wire of the downpipe is always in working state, and its own quality is poor, the failure rate of the electric heating wire of the downpipe is very high. As the original downpipe was long, once its electric heating wire failed, in the low temperature environment, the water entering the downpipe began to freeze again before it could flow away, and the defrosting could not be realized normally all the time.
Improvement measures:
1. The main reason why the evaporator cannot melt frost is that the quality of electric heating is saved in the problem, and the series method is used. Therefore, we should use the heating tube with rated voltage of 220v and use parallel connection.
2. Re-customize the water collecting plate to ensure that the water from the evaporator defrosting will not freeze twice after it reaches the water collecting plate.
3. The improved cut-off of the downpipe is to shorten the downpipe as much as possible, add another collecting bucket under the collecting pan, and replace the new collecting bucket before the water in the collecting bucket is full.

The last one:Cold storage structure and main equipment
Next:Key points of oil replacement in screw refrigeration compressor

Return list

Recommended for you

  • Mobile web site

  • The official WeChat

版權(quán)所有: 江蘇利邦機(jī)電設(shè)備有限公司 Copyright ? 2018 蘇ICP備18027510號(hào)-1

主站蜘蛛池模板: 肇庆市| 罗山县| 扎囊县| 靖安县| 滨海县| 灌云县| 油尖旺区| 万年县| 天津市| 旬阳县| 枝江市| 右玉县| 陕西省| 兴安盟| 上饶市| 上栗县| 嵊泗县| 北安市| 宁强县| 游戏| 凤翔县| 淮滨县| 苍梧县| 武鸣县| 都安| 镇江市| 焦作市| 祥云县| 鄂尔多斯市| 聂拉木县| 凯里市| 长宁县| 新河县| 临猗县| 武陟县| 南阳市| 久治县| 清徐县| 长泰县| 凤山县| 平果县|